September, 2020

Organo Deepali

Organo is an eco-habitat community focusing its efforts towards designing, building and developing sustainable habitats.

These reports explain the performance of the building under various exisitng circumstances for which recommendations are given through rigorous iterations. Results for important aspects like the indoor operative air temperature, air flow & heat analysis and daylighting are taken and analysed giving out appropriate design recommendations in the end.

*The following information of this project is a brief representation of the extensive report.

Indoor Operative Temperature Analysis —

Info

The data is considered for the average temaperature on May 23rd for different iterations. There is slight improvement in the temperature when naturally ventilated with the recommendations. The double galzing and the internal blinds with 1m overhangs helps in preventing the direct exposure of sunlight into the building.


*Note: The temperature in all rooms will have a good effect with the usage of blinds, curtains etc to reduce the direct heat gain during the hotter days. Natural ventilation and AC is run in a scheduled manner under regulated conditions to produce optimum results.

Average Temperature Comparison
May 23rd
Outside temperature 35.01°C

Iteration_01 - Natural Ventilation - Double glazing with internal window shading (the high reflective blinds fixed mid pane) and 1m overhangs over all windows.

Iteration_02 - Natural Ventilation & AC - Double glazing with internal window shading (the high reflective blinds fixed mid pane) and 1m overhangs over all windows.

Exterior Air Flow & Heat Analysis —

North

Wind Direction

|

Exterior

The image shows the interaction of the air in the balconies that are placed in the west. The first floor room balconies engages with more air due to the natural flow of air while hitting an object. (downward to upward). The outdoor patio and the FF lounge engages the most air in the west side of the building along with the first floor balconies.

Hue

Velocity

0.00 0.43 0.86 1.29 1.72 2.15 2.58 3.01 3.44 3.87 4.30 4.74

Pressure

-13.30 -11.49 -9.68 -7.87 -6.06 -4.25 -2.44 -0.63 1.17 2.98 4.79 6.60

Hue

Velocity

Pressure

0.00 -13.30
0.43 -11.49
0.86 -9.68
1.29 -7.87
1.72 -6.06
2.15 -4.25
2.58 -2.44
3.01 -0.63
3.44 1.17
3.87 2.98
4.30 4.79
4.74 6.60

North

Wind Direction

|

Exterior

As the predominant wind direction is from West to East, there is a velocity drop in the East side of the building. The diagram clearly shows how air if flowed through the building. The blue lines show the dip in the velocity of the air. The outdoor patio and the FF lounge on the west recieves good air flow.

Hue

Velocity

0.00 0.43 0.86 1.29 1.72 2.15 2.58 3.01 3.44 3.87 4.30 4.74

Hue

Velocity

0.00
0.43
0.86
1.29
1.72
2.15
2.58
3.01
3.44
3.87
4.30
4.74

Daylight Maps —

Samples of the Study and Analysis done for the M.Bedroom GF

North | Base case

North | Iteration: Increased window sizes for better daylight coverage

The ideal useable lux values for a residence ranges between 110 lux - 2200 lux. Anything more than 2200 lux or less than 110 lux is not suitable and is considered uncomfortable daylighting.

The darkest spots in the daylighting maps of the rooms indicate the spaces that recieves less than 110 lux which is not sufficient and would require artificial lighting in those places. Although more than 50% of the room area recieves daylight after iteration therefore the minor spots can be neglected based on the requirements.

Interior Air Flow & Heat Analysis —

Velocity, Pressure & Temperature

Temperature

Velocity

North

Master Bedroom GF

The temperature is almost evenly distributed across the room except for the areas near the windows. The air flow is slightly lesser compared to the other bedroooms but widely spread across the room.

Hue

Velocity

0.00 0.02 0.03 0.05 0.07 0.08 0.10 0.12 0.13 0.15 0.17 0.18

Pressure

-0.03 -0.03 -0.02 -0.01 0.00 0.01 0.02 0.03 0.03 0.04 0.05 0.06

Temperature

15.18 15.64 16.09 16.54 17.00 17.45 18.91 18.36 18.82 19.27 19.73 20.18

Hue

Velocity

Pressure

Temperature

0.00 -0.03 15.18
0.02 -0.03 15.64
0.03 -0.02 16.09
0.05 -0.01 16.54
0.07 0.00 17.00
0.08 0.01 17.45
0.10 0.02 18.91
0.12 0.03 18.36
0.13 0.03 18.82
0.15 0.04 19.27
0.17 0.05 19.73
0.18 0.06 20.18

North

|

Living & Dining Room

Air drawn out

|

Air drawn in

The above graphs depict the amount of air that is drawn in and out of the respective windows. The graph shows that the east window proves to intake more air than the north window indicating the west to east wind direction for the summer months. The line of air flow for the common spaces is achieved with cross ventilation.